120
Te
rm
inal assignment of
output ter
m
inal
190
RUN terminal
function selection
1
0
0 to 6, 8,
10 to 20,
25 to 28,
30 to 36, 39,
41 to 47,
64, 70, 84,
90 to 99,
100 to 106,
108,
110 to 116,
120,
125 to 128,
130 to 136,
139,
141 to 147,
164, 170,
184,
190 to 199,
9999
0, 100: Inverter running
1, 101: Up to frequency
2, 102: Instantaneous power failure/
undervoltage
3, 103: Overload alarm
4, 104: Output frequency detection
5, 105: Second output frequency detection
6, 106: Third output frequency detection
8, 108: Electronic thermal relay function
pre-alarm
10, 110:PU operation mode
11, 111: Inverter operation ready
12, 112:Output current detection
13, 113:Zero current detection
14, 114:PID lower limit
15, 115:PID upper limit
16, 116:PID forward/reverse rotation
output
17, —: Electronic bypass MC1
18, —: Electronic bypass MC2
19, —: Electronic bypass MC3
20, 120:Brake opening request
25, 125:Fan fault output
26, 126:Heatsink overheat pre-alarm
27, 127:Orientation in-position *
28, 128:Orientation error *
30, 130:Forward rotation output *
31, 131:Reverse rotation output *
32, 132:Regenerative status output *
33, 133:Operation ready 2
34, 134:Low speed output
35, 135:Torque detection
36, 136:In-position *
39, 139:Start time tuning completion
41, 141:Speed detection
42, 142:Second speed detection
43, 143:Third speed detection
44, 144:Inverter running 2
45, 145:Inverter running and start command
is on
46, 146:During deceleration at occurrence
of power failure (retained until
release)
47, 147:During PID control activated
64, 164:During retry
70, 170:PID output interruption
84, 184:Position control preparation ready *
90, 190:Life alarm
91, 191:Fault output 3 (power-off signal)
92, 192:Energy saving average value
updated timing
93, 193:Current average monitor signal
94, 194:Fault output 2
95, 195:Maintenance timer signal
96, 196:Remote output
97, 197:Alarm output 2
98, 198:Alarm output
99, 199:Fault output
9999: No function
0 to 99: Positive logic
100 to 199: Negative logic
* Available only when used with the FR-A7AP.
{
×
{
191
SU terminal
function selection
1
1
{
×
{
192
IPF terminal
function selection
1
2
{
×
{
193
OL terminal function
selection
1
3
{
×
{
194
FU terminal function
selection
1
4
{
×
{
195
ABC1 terminal
function selection
1
99
0 to 6, 8,
10 to 20,
25 to 28,
30 to 36, 39,
41 to 47, 64,
70, 84, 90,
91,
94 to 99,
100 to 106,
108,
110 to 116,
120,
125 to 128,
130 to 136,
139,
141 to 147,
164, 170,
184, 190,
191, 194 to
199, 9999
{
×
{
196
ABC2 terminal
function selection
1
9999
{
×
{
—
232 to 239
Refer to
Pr. 4 to Pr. 6
.
240
Refer to
Pr. 72
.
241
Refer to
Pr. 125
and Pr. 126
.
242, 243
Refer to
Pr. 73
.
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Para
meter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
mete
rs
{
: enabled
×
: disabled