117
Switch
between the
inverte
r oper
ation
and
electronic byp
ass oper
ation
to use
135
Electronic bypass
sequence selection
1
0
0
Without electronic bypass sequence
{
{
{
1
With electronic bypass sequence
136
MC switchover
interlock time
0.1s
1s
0 to 100s
Set the operation interlock time of MC2
and MC3.
{
{
{
137
Start waiting time
0.1s
0.5s
0 to 100s
Set the time slightly longer (0.3 to 0.5s or
so) than the time from when the ON signal
enters MC3 until it actually turns on.
{
{
{
138
Bypass selection at
a fault
1
0
0
Inverter output is stopped (motor coast) at
inverter fault.
{
{
{
1
Operation is automatically switched to
bypass operation at inverter fault
(Not switched when an external thermal
relay operation (E.OHT) or CPU fault
(E.CPU) occurs)
139
Automatic
switchover
frequency from
inverter to bypass
operation
0.01Hz
9999
0 to 60Hz
Set the frequency to switch inverter
operation to bypass operation.
{
{
{
9999
Without automatic switchover
159
Automatic
switchover
frequency range
from bypass to
inverter operation
0.01Hz
9999
0 to 10Hz
Valid during automatic switchover
operation (
Pr. 139
≠
9999)
When the frequency command decreases
below (
Pr. 139 - Pr. 159
) after operation is
switched from inverter operation to bypass
operation, the inverter automatically
switches operation to inverter operation
and operates at the frequency of frequency
command.
When the inverter start command (STF/
STR) is turned off, operation is switched to
inverter operation also.
{
{
{
9999
Valid during automatic switchover
operation (
Pr. 139
≠
9999)
When the inverter start command (STF/
STR) is turned off after operation is
switched from inverter operation to bypass
operation, operation is switched to inverter
operation and the motor decelerates to
stop.
—
140
to
143
Refer to
Pr. 29
.
144
Refer to
Pr. 37
.
Parameter u
ni
t
language switcho
ver
145
PU display
language selection
1
0
0
Japanese
{
×
×
1
English
2
Germany
3
French
4
Spanish
5
Italian
6
Swedish
7
Finnish
—
148,149
Refer to
Pr. 22
.
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Para
meter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
mete
rs
{
: enabled
×
: disabled