108
9.2 Manual Control of output
You will manually control each output.
*During the monitoring, the manual control is impossible.
*When the control type is compressor control or schedule control, there is no analog output function.
Do not manually control any analog output.
Caution
・
This function is available when the parent terminal is in the STOP status of control operation.
・
When you attempt to operate it in the RUN status, a message appears to ask whether to execute after the
status is changed to STOP. After the manual control operation, the control operation status never returns
to RUN. Therefore, manually change to RUN.
・
When the control type is schedule control, if the contact output is manually controlled and the control
operation status is changed to RUN, the change will be retained until the next control execution time comes.
(1) Click the
Manual control
button of an output you want to change.
(2) The following window appears.
Enter each item and then click the
Execute
button for manual control.
Caution
For analog voltage output, execute the manual control after the control unit starts the analog output since the
setting is written.
When the control unit does not start the analog output, the unit of output value is not displayed.
If, under such a condition, the analog output is manually controlled, an analog current output will be changed.
<For contact output>
<For analog output>
Item
Details
Output value
For contact output
Select a contact output status from the pull-down menu.
・
ON
・
OFF
For analog output
Enter an output value.
Setting range:
4.000 to 20.000 (Current output)
0.000 to 5.000 (Voltage output)