73
<Details on the control with the calendar setting>
This calendar function requires to set the valid and invalid time periods of control in the day.
For the valid control, it starts all the compressors with the loaded operating mode, and then executes the control by the
upper/lower limit monitoring.
For the invalid control, all the compressors are switched to the stop mode.
When this function is not activated, all the compressors are in the stop mode and the control by the upper/lower limit
monitoring is not executed.
It is necessary to set the calendar settings for two years at one time.
The settings will be configured in the following way:
①
Create a day pattern, which sets the valid and invalid time periods of control in the day.
A maximum of four day patterns can be created.
②
Assign the day pattern to each day to create the week pattern. With the created week pattern, the control is executed
for two years.
③
To any dates not applied to the pattern set at
②
, the day pattern is assigned.
Calendar setting
➝
0:00
24:00
8:00
17:00
Day pattern 1: Weekday
Valid
(Control by the upper/lower
limit monitoring)
Invalid
Invalid
Week pattern
Day
Sun
Mon
Tue
Wed
Thu
Fri
Sat
Pattern
Holiday Weekday Weekday Weekday Weekday Weekday Holiday
0:00
24:00
Day pattern 2: Holiday
Invalid
Date of control execution
different from the week pattern
Date
Pattern
March 20, 2020
Holiday
・
・
・
・
・
・
February 11, 2022
Holiday
For two years
②
②
③
①
①
March 2020
Sun Mon Tue Wed Thu
Fri
Sat
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
February 2022
Sun
Mon
Tue
Wed
Thu
Fri
Sat
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
262
27
28