116
(2) Connect the target control unit and the computer with a LAN cable.
*Set the computer’s IP address in order to be in the same network.
(3) Enter a password to each input field of
Password before change
,
Changed password
, and
Changed password (for
confirmation)
.
A maximum of 20 characters are allowed in the input field.
*The default password is
ecopass
.
(4) Click the
Change
button.
(5) After the change has been completed, the following message appears.
Click the
OK
button to close the message.
10.4 Setting of Logging Unit
You will set the logging ID for the logging unit (EMU4-LM) connected to the parent terminal unit.
On the following window, it is possible to clear the logging data.
*This setting is required when the parent terminal is combined with the logging unit.
*For details on the logging ID, refer to
Logging Unit for Energy Measuring Unit User’s Manual (Details).
*This function is available when the parent terminal is in the STOP status of control operation.
If you attempt to execute it in the RUN status, a message will appear to ask whether to execute after the status is changed
to STOP.
(1) Connect the target control unit and the computer with a LAN cable.
*Set the computer’s IP address in order to be in the same network.
(2) Enter the password for maintenance.