66
(
d
)
Click the
OK
button to determine the standard measuring point.
Return to the conditional expression setting window.
(
e
)
Select
ON
or
OFF
from the pull-down menu.
(
f
)
Click the
OK
button to determine the settings and close the window.
(4) When multiple conditional expressions are set at (3) above, set the combination of each conditional expression with the
radio button.
Item
Details
OR
If either of the conditional expressions is met, the contact output will be switched to ON.
AND
If both of the conditional expressions are met, the contact output will be switched to ON.
(5) Set the control delay time for the ON/OFF contact output execution.
The setting ranges from 0 to 3,600 seconds.
(6) Click the
Register
button to save the settings.
Useful function: Copy of interlocking control (contact output)
The following procedure is used to copy any desired control setting of contact output.
(1) Select a control setting of contact output to copy. Press the
Ctrl
and
C
key in that state.
(2) Select a field of no registration.
*It is impossible to copy to an analog output field.
(3) Press the
Ctrl
and
V
key. The selected control setting at (1) has been copied.