(3) Select a compressor for setup and then enter each item.
After the input, click the
Apply
button to save the settings.
Item
Details
Name
Enter a name to register the compressor.
A maximum of 30 characters are allowed in the input field.
Contact assignment
Set the terminal and contacts to control the compressor.
Terminal
Select a control unit to control the compressor from the pull-down menu.
The control unit registered to other compressor cannot be selected repeatedly.
Load/Unload DY
Select a contact number to control the state.
*For each contact operation, refer to Contact state corresponding to the compressor
operation mode below.
Register each contact without using the same contact number repeatedly.
The setting range: 1 to 3
*<Default> Load/Unload:1, Operation: 2, Stop: 3
Operation DY
Stop DY
Start/Stop priority
Set the order to control the compressor.
The order is determined through the following process:
・
A compressor with higher priority (with small number) is controlled first.
・
In the case that there are some compressors with the same priority, the one with small
ID is controlled first.
The setting range: 1 to 4
(4) Execute the same operation as (3) above for each compressor.
Contact state corresponding to the compressor operation mode
The following table shows the contact output states corresponding to the compressor operation modes.
The explanation here is an example of using the following settings:
Load/Unload DY: 1
Operation DY: 2
Stop DY: 3
Operation mode of
compressor
Contact number
Loaded
operating mode
Unloaded
operating mode
Stop mode
1
ON
OFF
OFF
2
ON
ON
OFF
3
ON
ON
OFF