61
<Control timing delay setting>
For the contact output, setting the delay time for ON and delay time for OFF enables to delay the control execution timing.
When the control unit collects the next measurement value and ends a determination by the conditional expression, if the
determination are different from a scheduled output, a new output determination will be employed.
00 min
Threshold
Measurement value
Collected
Action of control unit
Collect a measurement
value and the
conditional expression
determines the output.
Collect a measurement
value and the
conditional expression
determines the output.
Output
control
(OFF)
Output
control
(ON)
Output
control
(ON)
[Conditional expression]
When a measurement value exceeds the threshold, the contact output is ON.
Delay time for ON: None
Delay time for OFF: None
01 min
Collected
Collected
Control
Control
59 min
Collect a measurement
value and the
conditional expression
determines the output.
The delay of 60 seconds from the original control timing
[Conditional expression]
When a measurement value exceeds the threshold, the contact output is ON.
Delay time for ON: 60 seconds
Delay time for OFF: 60 seconds
Control (ON)
If the determination result
(ON/OFF) is switched during the
delay time, the latest
determination will be employed.
59 min
00 min
01 min
02 min
Threshold
Measurement
value
Action of
control unit
Collect a measurement value
and the conditional expression
determines the output.
Output control
(ON)
Control (OFF)
Control (ON)
Control (ON)
Output control
(ON)
Collect a measurement value
and the conditional expression
determines the output.
Collect a measurement value
and the conditional expression
determines the output.
Collect a measurement value
and the conditional expression
determines the output.
Collected
Collected
Collected
Collected
[Conditional expression]
When a measurement value exceeds the threshold, the contact output is ON.
Delay time for ON: 90 seconds
Delay time for OFF: 90 seconds
Control (ON)
If the determination result (ON/OFF) is
switched during the delay time, the
latest determination will be employed.
59 min
Threshold
Measurement
value
Action of
control unit
Collect a measurement value
and the conditional expression
determines the output.
Output control
(ON)
(ON)
Control (OFF)
Control (ON)
Control (ON)
Output control
(ON)
Collect a measurement value
and the conditional expression
determines the output.
Collect a measurement value
and the conditional expression
determines the output.
Collect a measurement value
and the conditional expression
determines the output.
Collected
Collected
The delay of 90 seconds from the original control timing
Collected
Collected
00 min
01 min
02 min