67
9-5-1. Energy Management Data List
Table 9-1 below summarizes the energy-control-related items that can be output in a CSV format, their
measurement units, and their data ranges for each data type.
Table 9-2 below summarizes how many months/years worth of data each CSV file can contain.
Table 9-1 Data items
Unit type
Item
Data type (intervals)
Measurement
unit
Data range
*12
5-minute
30-minute
1-day
*7
1-month
*8
1-year
*9
Outdoor unit
Data 1
*1
V
V
V
V
V
–
0–999999.99
Data 2
*1
V
V
–
0–9999.99
Data 3
*1
V
V
V
V
V
–
0–99.99
Outdoor temperature
V
V
*2
V
*3
V
*4
ºC, ºF
-100.0–1000.0
Indoor unit
Cooling set temperature
V
V
*2
V
*3
V
*4
ºC, ºF
-100.0–1000.0
Heating set temperature
V
V
*2
V
*3
V
*4
ºC, ºF
-100.0–1000.0
Room temperature
V
V
*2
V
*3
V
*4
ºC, ºF
-100.0–1000.0
Fan operation time
V
*10
V
*11
V
*11
V
*11
Minute
0–2147483647
Cooling operation time
V
*10
V
*11
V
*11
V
*11
Minute
0–2147483647
Heating operation time
V
*10
V
*11
V
*11
V
*11
Minute
0–2147483647
Thermo-ON time
V
*10
V
*11
V
*11
V
*11
Minute
0–2147483647
Cooling Thermo-ON time
V
*10
V
*11
V
*11
V
*11
Minute
0–2147483647
Heating Thermo-ON time
V
*10
V
*11
V
*11
V
*11
Minute
0–2147483647
Number of Thermo-ON/OFF
*6
V
*10
–
0–2147483647
Capacity-save value
V
*10
V
*11
V
*11
V
*11
Minute
0–21474836.47
Cooling capacity-save value
V
*10
V
*11
V
*11
V
*11
Minute
0–21474836.47
Heating capacity-save value
V
*10
V
*11
V
*11
V
*11
Minute
0–21474836.47
Apportioned electric energy
V
*10
V
*11
V
*11
V
*11
kWh
0–999999.9999
Target electric energy
V
*11
V
*11
V
*11
kWh
0–214748.3647
MCP
(PI controller)
MCP 1
V
*10
V
*10
V
*11
V
*11
V
*11
kWh, m3, MJ
0–999999.99
MCP 2
V
*10
V
*10
V
*11
V
*11
V
*11
kWh, m3, MJ
0–999999.99
MCP 3
V
*10
V
*10
V
*11
V
*11
V
*11
kWh, m3, MJ
0–999999.99
MCP 4
V
*10
V
*10
V
*11
V
*11
V
*11
kWh, m3, MJ
0–999999.99
MCT
(AI controller)
MCT 1
V
V
*2
V
*3
V
*4
ºC, ºF, %
-100.0–1000.0
MCT 2
V
V
*2
V
*3
V
*4
ºC, ºF, %
-100.0–1000.0
AHC
AHC temperature 1
V
V
*2
V
*3
V
*4
ºC, ºF
-100.0–1000.0
AHC temperature 2
V
V
*2
V
*3
V
*4
ºC, ºF
-100.0–1000.0
*1 The values are only for factory use. Do not use the values as reference.
*2 The values are the temperature or humidity values obtained every hour and half hour.
*3 The values are the average daily values of the temperature or humidity values obtained every hour.
*4 The values are the average monthly values of the average temperature or humidity values obtained every day
*3
.
*5 The values are the maximum values of the electric power consumption obtained in 1-minute increments during each period.
*6 "Number of Thermo-ON/OFF" is the number of times the unit has gone from Thermo-OFF to Thermo-ON.
*7 If the data contains the data for the current day, the data will be output that were collected up to the point of time when the CSV file was downloaded.
*8 The data for the current month will contain the data that were collected up to the point of time when the CSV file was downloaded.
*9 The data for the current year will contain the data that were collected up to the point of time when the CSV file was downloaded.
*10 Each value is a cumulative value after the start of operation. If the value exceeds the maximum value, it will wrap around to zero.
*11 Each value is a total value for each time period (1-day, 1-month, or 1-year).
*12 The number of digits that will be shown after the decimal point varies with the data item. For example, if the data range is "0–99.99," two digits after the
decimal point will be shown.
Table 9-2 Data period
Data type (intervals)
Data period
5-minute
Last 2 months
30-minute
Last 25 months
1-day
Last 25 months
1-month
Last 25 months
1-year