43
(4) Setting the contents of the schedule
Click [Edit] in the Contents of Schedule section to display the schedule settings screen.
Schedule settings
Scheduled start time
OK
Set the start time to apply to the schedule, set the operations to be scheduled, and then press [OK].
The operations that can be scheduled for air conditioning unit groups are as follows: ON/OFF/Optimized Start,
Mode, Set Temp, Air Direction, Fan Speed, and Prohibit Remote Controller Operation.
Up to 24 events can be scheduled per day.
Note: The operation items that will appear on the screen vary, depending on the group type.
Note: [Optimized Start] can be selected only for the air conditioning unit groups.
Note: If [Optimized Start] is selected, the operation mode and the set temperature need to be set as well. The Optimized
Start function will start the units 5 to 60 minutes prior to the scheduled start time to reach the set temperature at
the scheduled start time, based on the operation data in the past. (When the units start the first time after a power
reset, the units will start operation 30 minutes before the scheduled start time.)
If the room temperature is measured by the return air temperature sensor on the air conditioning unit, the
measured value may not be an accurate representation of the temperature in the room, especially when the air
conditioning unit is stopped and the room air is stagnant. When this is the case, use an external temperature
sensor (PAC-SE40TSA) or remote controller sensor to measure the room temperature.
Note: If [Optimized Start] is selected and the [Prohibit Remote Controller Operation] setting is set to Prohibit or Permit
at the same time, the operations from the remote controllers will be prohibited or permitted at the scheduled start
time.
Note: When setting a schedule for a block or all groups, all operation modes are available for selection, but the available
operation modes depend on the unit model. The units will not operate in the selected mode not supported by the
units.
Note: For LOSSNAY unit groups, the item [Set Temp.] or [Air Direction] will not appear, and only ON/OFF setting under
the Prohibit Remote Controller Operation can be made.
Note: For general equipment groups, only the operation ON/OFF settings can be made.
Note: The scheduled operations will continue to be in effect unless they are overwritten by the other schedule settings or
the operation settings are changed on the Web browser. Be sure to set the contents of schedule in a way that will
not impact on the next day's operation. For example, if Prohibit setting of remote controller operation is made for
any time such as 17:00, Permit setting needs to be made for any time before the date changes such as 23:59.