16
4-1-3. Operating the units in a given group
In the Overview display of the Condition List screen, click one of the group icons to display its operation settings
screen, which shows the current operation conditions. Change the desired settings and click [OK] to reflect the
changes. Click [Cancel] to return to the previous screen without making any changes.
Note: Only the ON/OFF operation is possible for general equipment groups. The general equipment whose prohibition
setting is enabled ([Allow operations] is set to [No operations] on the group settings screen, accessible via the
Web Browser for Initial Settings) cannot be operated.
Group name
Set temperature
ON/OFF
Block name
Interlocked LOSSNAY
ON/OFF
Fan speed of interlocked
LOSSNAY
Operation mode
Prohibit Remote Controller
Operation
Air direction
Filter Sign Reset
Hold
Cancel
Click to return to the
previous screen without
making any changes.
Fan speed
OK
Click to reflect the changes
made.
Item
Description
ON/OFF
Click [ON] or [OFF] to turn on or off the units in a given group.
Note: Switching this switch will turn on or off the LOSSNAY unit as well that is interlocked with
the operation of indoor units in the group. To turn on or off the LOSSNAY unit only, use the
"Interlocked LOSSNAY ON/OFF" switch.
Operation mode
*1
Click the desired operation mode.
Air conditioning unit: Cool, Dry, Fan, Heat, Auto, Setback
LOSSNAY unit: Heat Recovery, Bypass, Auto
Air To Water (PWFY) unit: Heating, Heating ECO, Hot Water, Anti-freeze, Cooling
Note: Only the operation modes available for the unit model will appear.
Note: The Setback mode can be selected on the EB-50GU-A, but not on the EB-50GU-J.
Set temperature
*1
Click
or
to adjust the set temperature of the air conditioning unit or the Air To
Water (PWFY) unit.
Note: The settable temperature ranges depend on the unit model.
Note: If the indoor unit supports the dual set point function in the AUTO mode and when the
operation mode above is set to Auto or Setback, two set temperatures for Cool mode and
Heat mode can be set.
Note: The temperature unit (°C or °F) can be selected on the Basic System settings screen,
accessible via the Web Browser for Initial Settings.
Air Direction
*1
Click
or
to adjust the air direction.
(Mid 3)
(Mid 2)
(Mid 1)
(Mid 0)
(Horizontal)
(Swing)
(Auto)
Note: Available air directions depend on the unit model.