S
-Series
Cooling or Heating
Heat pump
• Features ∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
P.92 - P.96
• Optional parts ∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
P.94
• Specifications
PUMY-SP VKMD-A (-BS)/YKMD-A (-BS)
∙∙∙∙∙∙∙∙
P.97 - P.98
PUMY-P VKM5 (-BS)/YKM4 (-BS)/YKMD-A (-BS)
∙∙∙∙∙∙∙
P.99 - P.100
*For P140 and P200 models
Outdoor unit
Indoor
unit
Between indoor units
top-bottom differential
15m [49ft]
Furthest indoor from outdoor
90m [295ft]
(equivalent length)
(actual length 70m [230ft])
Top-bottom
differential
50m [164ft] *1
Outdoor unit
Indoor
unit
Between indoor units
top-bottom differential
15m [49ft]
Furthest indoor from outdoor
175m [574ft]
(equivalent length)
(actual length 150m [492ft])
Top-bottom
differential
50m [164ft] *2 *3
Outdoor unit
Indoor
unit
Between indoor units
top-bottom differential
15m [49ft]
Furthest indoor from outdoor
90m [295ft]
(equivalent length)
(actual length 80m [262ft])
Top-bottom
differential
50m [164ft] *2
• System Pipe Lengths
Refrigerant Piping Lengths
Total length
Furthest indoor from outdoor
Furthest indoor from first branch
Vertical differentials between units
Indoor/outdoor (outdoor higher)
Indoor/outdoor (outdoor lower)
Indoor/indoor
Maximum meters [Feet]
120 [394]
70 (90 equivalent) [230 (295)]
50 [164] *4
Maximum meters [Feet]
50 [164]
30 [98]
15 [49]
[SP80~140(VKMD-A/YKMD-A)]
Refrigerant Piping Lengths
Total length
Furthest indoor from outdoor
Furthest indoor from first branch
Vertical differentials between units
Indoor/outdoor (outdoor higher)
Indoor/outdoor (outdoor lower)
Indoor/indoor
Maximum meters [Feet]
300 [984]
150 (175 equivalent) [492(574)]
30 [98]
Maximum meters [Feet]
50 [164]
40 [131] *3
15 [49]
[P112~140(VKM5/YKM4)]
Refrigerant Piping Lengths
Total length
Furthest indoor from outdoor
Furthest indoor from first branch
Vertical differentials between units
Indoor/outdoor (outdoor higher)
Indoor/outdoor (outdoor lower)
Indoor/indoor
Maximum meters [Feet]
150 [492]
80 (90 equivalent) [262(295)]
30 [98]
Maximum meters [Feet]
50 [164]
40 [131]
15 [49]
[P200YKMD-A]
*1 When the outdoor unit is installed below the indoor unit, top-bottom differential is 30m [98ft].
*2 When the outdoor unit is installed below the indoor unit, top-bottom differential is 40m [131ft].
*3 30m [98ft] or less if PKFY-P*VLM, PFFY-P*VKM, PFFY-P*VL* type of indoor units are included.
*4 Use liquid pipe of ø9.52 for less than P50 indoor units, when farthest length from the first joint exceeds 30 m.
• Small offices
The CITY MULTI S-Series (for small applications) makes use of a two-pipe refrigerant system, which allows for system
changeover from cooling to heating, ensuring that a constant indoor climate is maintained in all zones. The compact
outdoor unit utilizes R410A refrigerant and an inverter-driven compressor for effective energy use.
With a wide lineup of indoor units connected to a flexible piping system, the CITY MULTI Series can be configured to suit
diverse applications. Thanks to the individual operation of up to 12 units* and a group change function, the CITY MULTI
S-Series can flexibly accommodate layout changes in stores and offices.
Cooling/heating changeover system with horizontal airflow for
small offices and stores
1-fan type
2-fan type
91
VRF
Y-Series
VRF
Lineup
VRF
R2-Series
VRF
Zubadan
VRF
WY-Series
VRF
WR2-Series
VRF
S-Series
VRF
Indoor Units
Ventilation
Systems
Technologies and Functions
Remote Controller
Hot Water Solution
VRF
BC Controllers
VRF
S-Series
Summary of Contents for City Multi R2 Series
Page 1: ...CM20AN E NZ VRF City Multi Product Catalogue ...
Page 101: ...BC Controllers 101 ...
Page 112: ...Indoor Units VRF 112 ...
Page 114: ...Ceiling Cassette Type 4 Way Airflow Type 114 ...
Page 122: ...Ceiling Cassette Type 2 Way Airflow Type 122 ...
Page 128: ...Ceiling Concealed Type 128 ...
Page 150: ...Wall Mounted Type 150 ...
Page 154: ...Floor Standing Type 154 ...
Page 181: ...Ventilation Systems 181 ...
Page 190: ...Remote Controllers 190 ...