Model
PWFY-EP100VM-E1-AU
Power source
Heating capacity (Nominal)
Temp. range of heating
Cooling capacity (Nominal)
Temp. range of cooling
Connectable outdoor unit/
heat source unit
Sound pressure level (measured in anechoic room)
Diameter of refrigerant pipe
Diameter of water pipe
Field drain pipe size
External finish
External dimension H × W × D
Net weight
Circulating water
Design pressure
Drawing
Standard attachment
Optional parts
Remark
kW
kcal / h
BTU / h
kW
A
W.B.
W.B.
-
-
-
kW
kcal / h
BTU / h
kW
A
D.B.
D.B.
-
-
-
*1
*1
*1
Power input
Current input
Outdoor temp.
for outdoor unit
Inlet Water temp.
for heat source unit
Inlet Water temp. for PWFY
Power input
Current input
Outdoor temp.
for outdoor unit
Inlet Water temp.
for heat source unit
Inlet Water temp. for PWFY
Total capacity
Model / Quantity
*2
*2
*2
dB <A>
mm (in.)
mm (in.)
mm (in.)
mm (in.)
mm (in.)
mm
in.
kg (lbs)
m
3
/ h
MPa
MPa
Operation Volume Range
R410A
Water
External
Wiring
Document
Accessory
Liquid
Gas
Inlet
Outlet
1 - phase 220 - 230 - 240V 50 / 60Hz
12.5
10,800
42,700
0.015
0.068 - 0.065 - 0.063
-20 ~ 32°C (-4 ~ 90°F) R2-Series
-20 ~ 15.5°C (-4 ~ 60°F) Y-Series
10 ~ 45°C (50 ~ 113°F) WR2-Series
10 ~ 45°C (50 ~ 113°F) WY-Series
10 ~ 40°C (50~104°F) R2/Y/WR2/WY-Series
11.2
9,600
38,200
0.015
0.068 - 0.065 - 0.063
-5 ~ 46°C (23 ~ 115°F) R2-Series
-5 ~ 46°C (23 ~ 115°F) Y-Series
10 ~ 45°C (50 ~ 113°F) WR2-Series
10 ~ 45°C (50 ~ 113°F) WY-Series
10 ~ 35°C (50 ~ 95°F)
50~100% of outdoor/heat source unit capacity
PUHY-P•Y(S)NW-A1(-BS), PUHY-EP•Y(S)NW-A1(-BS),
PQHY-P•Y(S)LM-A1, PURY-(E)P•Y(S)NW-A1(-BS), PQRY-P•Y(S)LM-A1
29
ø9.52 (ø3/8") Brazed
ø15.88 (ø5/8") Brazed
R1 (R3/4 without expansion joint)
Rc1 (Rc3/4 without expansion joint)
ø32 (1-1/4")
NO
800 (785 without legs) × 450 × 300
31-1/2" (30-15/16" without legs) × 17-3/4" × 11-13/16"
33 (73)
1.8 ~ 4.30
4.15
1.00
WKJ94T340
WKE94C951
Installation Manual, Instruction Book
Strainer, Heat insulation material, Expansion joint, Flow switch × 1 set, Buffer material
Solenoid valve kit: PAC-SV01PW-E
Details on foundation work, duct work, insulation work, electrical wiring, power source
switch, and other items shall be referred to the Installation Manual.
Note:
*1Nominal heating conditions (PWFY conditions are indicated in the parentheses. )
<Y/R2-Series>
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
(Inlet water Temp. 30°C (87°F), Water flow rate 4.30m
3
/h)
* Due to continuing improvement, the above specifications may be subject to change without notice.
* The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C (32°F) or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use ground water and well water.
* Install the outdoor unit (R2-Series) in an environment where the wet bulb Temp. will not exceed 32°C (90°F).
* The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
<WY/WR2-Series>
Inlet water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
(Inlet water Temp. for PWFY side 30°C (87°F), Water flow rate 4.30m
3
/h)
*2Nominal cooling conditions (PWFY conditions are indicated in the parentheses. )
<Y/R2-Series>
Outdoor Temp. : 35°CDB (95°FDB)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
(Inlet water Temp. 23°C (73°F), Water flow rate 3.86m
3
/h)
<WY/WR2-Series>
Inlet water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
(Inlet water Temp. for PWFY side 23°C (73°F), Water flow rate 3.86m
3
/h)
BTU / h =kW × 3,412
cfm
=m
3
/ min × 35.31
lbs
=kg / 0.4536
* The specification data is subject
to rounding variation.
Unit converter
HEX unit
Solenoid valve is not installed
PWFY-EP100VM-E1-AU
222
SPECIFICATIONS
Summary of Contents for City Multi R2 Series
Page 1: ...CM20AN E NZ VRF City Multi Product Catalogue ...
Page 101: ...BC Controllers 101 ...
Page 112: ...Indoor Units VRF 112 ...
Page 114: ...Ceiling Cassette Type 4 Way Airflow Type 114 ...
Page 122: ...Ceiling Cassette Type 2 Way Airflow Type 122 ...
Page 128: ...Ceiling Concealed Type 128 ...
Page 150: ...Wall Mounted Type 150 ...
Page 154: ...Floor Standing Type 154 ...
Page 181: ...Ventilation Systems 181 ...
Page 190: ...Remote Controllers 190 ...