PLFY-P15-50VFM-E1
245 mm
Horizontal
airflow
Horizontal
airflow
• Airflow distribution
Horizontal airflow
Compact & light-weight design
0
1
2
3
4
0
1
2
2.7
(m/s)
Floor distance (m)
Height (m)
0.5
1.0
2.0
1
2
3
4
2.0
0.5
1.0
600 mm
600 mm
Cold air
doesn’t affect
me directly.
<Cooling mode>
Horizontal
Ceiling height: 2.7 m
• Horizontal airflow
Beautiful square design
The above-ceiling height of 245 mm is top class in the industry*
and fits into narrow ceiling spaces.
* As of Aug 2015, among compact 4-way cassettes
for system ceilings. (In-company survey)
Supply air is horizontally fed into the room to reduce the cold draft feeling. This airflow is ideal for offices and restaurants.
The panel weighs 3 kg, and the main unit weighs 14 kg (P15,
P20 and P25 models) or 15 kg (P32, P40 and P50 models).
These weights are 5 kg lighter than the PLFY-VEM-E model,
allowing easy suspension.
Above-ceiling height of 245 mm
The square design matches 2 × 2 (600 mm × 600 mm) ceiling
construction specifications.
As such it can be seamlessly integrated to match the design of direct
line lighting systems to creating a streamlined look and feel.
Ceiling cassette type
4-way airflow type
PLFY-P VFM-E1
• Technologies and functions
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙ P.167
The compact size offers a perfect fit to grid system ceilings
(600 mm × 600 mm) and provides 4-way airflows despite its size.
Optional
121
VRF
Y-Series
VRF
Lineup
VRF
R2-Series
VRF
Zubadan
VRF
WY-Series
VRF
WR2-Series
VRF
S-Series
VRF
Indoor Units
Ventilation
Systems
Technologies and Functions
Remote Controller
Hot Water Solution
VRF
BC Controllers
VRF
S-Series
SPECIFICATIONS
PLFY-P15VFM-E1 PLFY-P20VFM-E1 PLFY-P25VFM-E1 PLFY-P32VFM-E1 PLFY-P40VFM-E1 PLFY-P50VFM-E1
Power source
1-phase 220-240V 50Hz / 220V 60Hz
Cooling capacity
*1
kW
1.7
2.2
2.8
3.6
4.5
5.6
*1 BTU/h
5,800
7,500
9,600
12,300
15,400
19,100
Heating capacity
*1
kW
1.9
2.5
3.2
4.0
5.0
6.3
*1 BTU/h
6,500
8,500
10,900
13,600
17,100
21,500
Power
Cooling
kW
0.02
0.02
0.02
0.02
0.03
0.04
consumption
Heating
kW
0.02
0.02
0.02
0.02
0.03
0.04
Current
Cooling
A
0.19
0.21
0.22
0.23
0.28
0.40
Heating
A
0.14
0.16
0.17
0.18
0.23
0.35
External fi nish
Unit
Galvanized steel sheet
(Munsell No.)
Panel
MUNSELL (1.0Y 9.2/0.2)
Dimension
Unit
mm(in.)
208 x 570 x 570 (8-1/4 x 22-1/2 x 22-1/2)
H x W x D
Panel
mm(in.)
10 x 625 x 625 (3/8 x 24-5/8 x 24-5/8)
Net weight
Unit
kg(lbs.)
14 (31)
15 (33)
Panel
kg(lbs.)
3 (7)
Heat exchanger
Cross fi n (Aluminum fi n and copper tube)
FAN
Type x Quantity
Turbo fan x 1
Airfl ow rate
m
3
/min
6.5-7.5-8.0
6.5-7.5-8.5
6.5-8.0-9.0
7.0-8.0-9.5
7.5-9.0-11.0
9.0-11.0-13.0
(Lo-Mid-Hi)
L/s
108-125-133
108-125-142
108-133-150
117-133-158
125-150-183
150-183-217
cfm
230-265-282
230-265-300
230-282-318
247-282-335
265-318-388
318-388-459
External static press.
Pa
0
Motor
Type
DC motor
Output
kW
0.05
Air fi lter
PP Honeycomb fabric (long life type)
Refrigerant
pipe diameter
Gas
(Flare) mm(in.)
ø12.7 (ø1/2)
Liquid
(Flare) mm(in.)
ø6.35 (ø1/4)
Field drain pipe diameter
mm(in.)
O.D. 32 (1-1/4) (PVC pipe VP-25 connectable)
Sound pressure level *2
dB<A>
26-28-30
26-29-31
26-30-33
26-30-34
28-33-39
33-39-43
(Lo-Mid-Hi)
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27°C(81°F)DB/19°C(66°F)WB,Outdoor 35°C(95°F)DB
Heating : Indoor 20°C(68°F)DB,Outdoor 7°C(45°F)DB/6°C(43°F)WB
*2 It is measured in anechoic room at power source 230V.
Notes:
Optional parts
Description
Model
Applicable models
i-see Sensor corner panel
PAC-SF1ME-E
P15, P20, P25, P32, P40, P50
Wireless signal receiver
PAR-SF9FA-E
P15, P20, P25, P32, P40, P50
Panel & Corner panel
With signal Receiver
With 3D i-see Sensor
With New Wireless
Remote Controller
Panel
SLP-2FA
SLP-2FAL
●
SLP-2FAE
●
SLP-2FALE
●
●
SLP-2FALM
●
●
SLP-2FALME
●
●
●
Corner panel
PAR-SF9FA-E
●
PAC-SF1ME-E
●
Ceiling cassette type
4-way airfl ow type
PLFY-P VFM-E1
Summary of Contents for City Multi R2 Series
Page 1: ...CM20AN E NZ VRF City Multi Product Catalogue ...
Page 101: ...BC Controllers 101 ...
Page 112: ...Indoor Units VRF 112 ...
Page 114: ...Ceiling Cassette Type 4 Way Airflow Type 114 ...
Page 122: ...Ceiling Cassette Type 2 Way Airflow Type 122 ...
Page 128: ...Ceiling Concealed Type 128 ...
Page 150: ...Wall Mounted Type 150 ...
Page 154: ...Floor Standing Type 154 ...
Page 181: ...Ventilation Systems 181 ...
Page 190: ...Remote Controllers 190 ...