IX
Troubleshooting ]
- 202 -
HWE0716A
GB
(5) Intelligent power module
Measure resistances between each pair of terminals on the IPM with a tester, and use the results for troubleshooting.
1) Notes on measurement
Check the polarity before measuring. (On the tester, black normally indicates plus.)
Check that the resistance is not open (
ohm) or not shorted (to 0 ohm).
The values are for reference, and the margin of errors is allowed.
The result that is more than double or half of the result that is measured at the same measurement point is not allowed.
2) Tester restriction
Use the tester whose internal electrical power source is 1.5V or greater
Use the dry-battery-powered tester.
(The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester, as the applied volt-
age is low.)
Use a low-range tester if possible. A more accurate resistance can be measured.
Judgment value (reference)
Black ( + )
P
N
U
V
W
Red (-)
P
-
-
5 - 200 ohm
5 - 200 ohm
5 - 200 ohm
N
-
-
U
5 - 200 ohm
-
-
-
V
5 - 200 ohm
-
-
-
W
5 - 200 ohm
-
-
-
External view
Internal circuit diagram
1 4 7 10 16
W
V
U
B
P
N
V
U
P
W
N
B
3
2
1
6
5
4
9
8
7
11
13
10
14
15
12
16
Drive circuit
Drive circuit
Drive circuit
Drive circuit
Drive circuit
Drive circuit
Overheating -protection
circuit
Temperature
sensor
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......