VII
Control ]
- 78 -
HWE0716A
GB
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed.
Setting of CN3D is required.(page 24)
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporating temperature setting that
corresponds to each combination.
5) Refer to VII [2] Controlling the Outdoor Unit -7- Defrost Operation Control for details.(page 87)
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SW3
1
Test run mode: en-
abled/disabled
SW3-2 disabled
SW3-2 enabled
Anytime after power on
A
-
2
Test run mode: ON/
OFF
Stops all ICs
Sends a test-run
signal to all IC
After power on and when
SW3-1 is on.
A
-
3
Defrost start temper-
ature
-10°C [14°F]
-5°C [23°F]
Anytime after power on
B
B
4
Defrost end temper-
ature
10°C [50°F]
15°C [59°F]
Anytime after power on
(except during defrost op-
eration)
B
B
5
Target evaporating
temperature setting
Depends on the setting combination with
the SW2-9 setting (Note 4)
Anytime after power on
A
-
6
Temperature unit
setting
°C
°F
Anytime after power on
C
C
7
Target condensing
temperature setting
for heating
49°C [120°F]
53°C [127°F]
-
A
-
8
-
-
-
-
-
-
9
Model setting
(To change the external
static pressure setting)
Outdoor standard
static pressure
Outdoor high static
pressure
Before being energized
C
C
10
Model setting
(To change the external
static pressure setting)
High static pressure
60Pa
High static pressure
30Pa
Before being energized
C
C
SW4
1
-
-
-
-
-
-
2
-
-
-
-
-
-
3
Refrigerant amount
adjustment
Normal operation
mode
Refrigerant amount
adjust mode
Anytime after being energized
(except during initial startup
mode.
Automatically cancelled 90
minutes after compressor
startup)
A
-
4
Low-noise mode/
step demand switch-
ing
Low-noise mode
(Note 3)
Step demand mode Before being energized
C
C
5
Automatic cooling/heat-
ing switchover (IC with
the minimum address)
Normal operation
mode
Automatic cooling/
heating switchover
Before being energized
A
-
6
Cumulative compressor
operation time data dele-
tion
Cumulative compressor
operation time data is
retained.
Cumulative compressor
operation time data is
deleted.
Anytime after power on (when
the unit is turned on)
C
C
7
-
-
-
-
-
-
8
-
-
-
-
-
-
9
-
-
-
-
-
-
10
-
-
-
-
-
-
Switch
SW2-9
OFF
ON
SW3-5
OFF
0°C [32°F]
-4°C [25°F]
ON
-2°C [28°F]
-6°C [21°F]
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......