II
Restrictions ]
- 41 -
HWE0716A
GB
HP144, HP192 models
Unit: m [ft]
Operation
Pipe sections
Allowable length of
pipes
Length
Between outdoor units
A+B
10 [32] or less
Total pipe length
A+B+C+D+E+F+G+I+J
+a+b+c+d+e+f+g+i
300 [984] or less
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
A(B)+C+G+I+J+i
150 [492] or less
(Equivalent length 175
[574] or less)
Total pipe length from the first branch to the far-
thest indoor unit (
)
G+I+J+i
40 [131] or less
Height
difference
Between indoor and outdoor units
H
50 [164] or less
(40 [131] or below if
outdoor unit is below in-
door unit)
Between indoor units
h1
15 [49] or less
Between outdoor units
h2
0.1[0.3] or less
Indoor Indoor Indoor Indoor
Indoor Indoor Indoor Indoor
C
L
H
a
h1
h2
b
2
1
c
3
d
4
e
5
f
6
g
7
i
8
C
D
E
F
G
I
J
B
A
First branch
(Note)
To downstream units
Note : "Total sum of downstream unit model numbers"
in the table is the sum of the model numbers
of the units after point E in the figure.
Note1 Install the pipe that connects the branch pipe and the outdoor units in
the way that it has a downward inclination toward the branch pipe.
Provide a trap on the pipe (gas pipe only) within 2 m from the
joint pipe if the total length of the pipe that connects the joint
pipe and the outdoor unit exceeds 2 m.
Downward inclination
To indoor unit
To indoor unit
To indoor unit
Joint pipe
Joint pipe
Trap
(gas pipe
only)
To indoor unit
Upward inclination
Gas refrigerant distributor
Liquid refrigerant distributor
2m[6ft]
2m[6ft] Max.
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......