1. Error
Code
ACCT sensor fault (Detail code 115)
2. Error definition and error detection method
When the formula "output current < 2 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy
Refer to section - 6 -"Inverter" under part [4] "Trouble shootiong principal parts" for error codes related to the
inverter.(page 196)
1. Error
Code
DCCT sensor fault (Detail code116)
2. Error definition and error detection method
When the bus current less than 18 Apeak is detected at startup (6Hz)
3. Cause, check method and remedy
Refer to section -6-"Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 196)
5301
Cause
Check method and remedy
(1)
Inverter open output phase
Check the output wiring connections.
(2)
Compressor failure
Refer to 9 [4]-6-(2)[2].(page 198)
(3)
INV board failure
Refer to 9 [4]-6-(2)[1].(page 198)
(4)
Contact failure
Check the connection of the connector (CNCT2) on the INV board.
(5)
ACCT sensor failure
Refer to 9 [4]-6-(4).(page 201)
5301
Cause
Check method and remedy
(1)
Contact failure
Check the contact of the connector (CNCT) on the INV board, and the
contact the connector on DCCT side.
(2)
Misorientation
Check the installation direction of DCCT.
(3)
DCCT sensor failure
Replace the DCCT sensor.
(4)
INV board failure
Replace the INV board.
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......