VIII
Test Run Mode ]
- 104 -
HWE0716A
GB
3. Amount of refrigerant to be added
The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units.
The amount necessary for extended pipe (field piping) is not included and must be added on site.
(1) Calculation formula
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
Round up the calculation result to the nearest 0.1kg. (Example: 18.04kg to 18.1kg)
Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz.
(Example: 178.21
Q\
to 179oz)
Outdoor unit model
HP72
HP96
Amount of pre-charged refrigerant in
the outdoor unit (kg)
9.0
9.0
Amount of pre-charged refrigerant in
the outdoor unit [lbs-oz]
19 - 13
19 - 13
Amount of added refrigerant (kg) = (0.2 x L
1
) + (0.12 x L
2
) + (0.06 x L
3
) + (0.024 x L
4
) +
ǩ
Amount of added refrigerant (oz) = (2.15 x L
1
' ) + (1.29 x L
2
' ) + (0.65 x L
3
' ) + (0.26 x L
4
' ) +
ǩ
L
1
: Length of ø15.88 [5/8"] liquid pipe (m)
L
2
: Length of ø12.7 [1/2"] liquid pipe (m)
L
3
: Length of ø9.52 [3/8"] liquid pipe (m)
L
4
: Length of ø6.35 [1/4"] liquid pipe (m)
ǩ
,
ǩ
' : Refer to the table below.
L
1
' : Length of ø15.88 [5/8"] liquid pipe [ft]
L
2
' : Length of ø12.7 [1/2"] liquid pipe [ft]
L
3
' : Length of ø9.52 [3/8"] liquid pipe [ft]
L
4
' : Length of ø6.35 [1/4"] liquid pipe[ft]
Total capacity of
connected indoor units
ǩ
(kg)
ǩ
'(oz)
-
30
2.0
71
31
-
60
2.5
89
61
-
126
3.0 106
127
-
150
3.5
124
151
-
184
4.5 159
185
-
242
5.0
177
243
-
272
6.0
212
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......