VIII
Test Run Mode ]
- 110 -
HWE0716A
GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-HP72THMU-A
PUHY-HP96THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected units
Unit
2
2
No. of units in operation
2
2
Model
-
112/112
140/140
Piping
Main pipe
m [ft]
5 [16-3/8 ]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
10 [32-3/4 ]
Total pipe length
25 [82]
25 [82]
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
[lbs-oz]
11.3 [25]
13.8 [30-1/2]
Outdoor
unit
Electric current
A
18.3
23.6
Voltage
V
230
230
Compressor frequency
Hz
55
72
LEV open-
ing
Indoor unit
Pulse
325/325
406/406
SC (LEV1)
0
0
LEV2
1400
1400
LEV4
0
0
Pressure
High pressure (after O/S)/low pres-
sure (before accumulator)
MPa
[psi]
2.81/0.66 [408/96]
2.87/0.67 [416/97]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
84 [183]
84 [183]
Heat exchanger outlet
(TH3)
-2 [28]
-3 [26]
Accumulator inlet
-2 [28]
-3 [26]
Accumulator outlet
-2 [28]
-3 [26]
Compressor inlet
-2 [28]
-3 [26]
Compressor shell bottom
40 [104]
40 [104]
Indoor
unit
LEV inlet
38 [100]
39 [102]
Heat exchanger outlet
80 [176]
80 [176]
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......