VIII
Test Run Mode ]
- 111 -
HWE0716A
GB
2. 2-unit
combination
(1) Cooling operation
Operation
Outdoor unit model
PUHY-HP144TSHMU-A
PUHY-HP72THMU-A
PUHY-HP72THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected units
Unit
4
No. of units in operation
4
Model
-
112/112/112/112
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
45 [147-5/8]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
20.9 [46-3/16]
Outdoor
unit
Electric current
A
34.9
Voltage
V
230
Compressor frequency
Hz
50
50
LEV open-
ing
Indoor unit
Pulse
325/325/325/325
SC (LEV1)
55
55
LEV2
1400
LEV4
0
Pressure
High pressure (after O/S)/low pres-
sure (before accumulator)
MPa
[psi]
2.77/0.74 [402/107]
2.77/0.74 [402/107]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
84 [183]
84 [183]
Heat exchanger outlet
(TH3)
47 [117]
47 [117]
Accumulator inlet
7 [45]
7 [45]
Accumulator outlet
7 [45]
7 [45]
SCC outlet (TH6)
25 [77]
25 [77]
Compressor inlet
19 [66]
19 [66]
Compressor shell bottom
40 [104]
40 [104]
Indoor
unit
LEV inlet
19 [66]
Heat exchanger outlet
6 [43]
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......