IX
Troubleshooting ]
- 198 -
HWE0716A
GB
(2) Inverter output related troubles
Items to be checked
Phenomena
Remedy
[1]
Check the INV
board error
detection cir-
cuit.
(1)
Disconnect the invert-
er output wire from
the output terminals
(U, V, W) of the IPM.
1)
IPM/overcurrent breaker trip
(4250 Detail code No. 101, 102,
103, 104, 105, 106, and 107)
See the section "Troubleshooting
the IPM" ( Refer to - 6 - (5)
).(page 202)Replace the IPM, and
put the outdoor unit back into oper-
ation.
If the problem persists, replace the
INV board.
(2)
Put the outdoor unit
into operation.
2)
Logic error
(4220 Detail code No. 111)
See the section "Troubleshooting
the IPM" ( Refer to - 6 - (5)
).(page 202)Replace the IPM, and
put the outdoor unit back into oper-
ation.
If the problem persists, replace the
INV board.
Replace the INV board, and put
the outdoor unit back into opera-
tion.
If the problem persists, replace the
DCCT.
3)
ACCT sensor circuit failure
(5301 Detail code No.117)
Replace the INV board.
4)
DCCT sensor circuit failure
(5301 Detail code No.118)
Replace the DCCT board.
Replace the DCCT, and put the
outdoor unit back into operation.
If the problem persists, replace the
INV board.
5)
IPM open
(5301 Detail code No.119)
Normal
[2]
Check for
compressor
ground fault or
coil error.
Disconnect the compres-
sor wiring, and check the
compressor Meg, and coil
resistance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
When no liquid refrigerant in the
compressor
Replace the compressor
Check that no liquid refrigerant in
the compressor.
2)
Compressor coil resistance failure
Coil resistance value of 0.16 ohm
(20°C [68°F])
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......