-5- Bypass Control
Solenoid valves are categorized into 3 types: High/low pressure bypass valve (SV1a), High/low pressure bypass valve via
heat exchanger (SV9), and circuit switch valve at subcool coil low pressure side (SV6). Refer to the following tables for each
valve operation.
(1) Bypass solenoid valve (SV1a) (ON = Open)
(2) Bypass solenoid valve (SV2) (ON = Closed)
Operation
SV1a
ON OFF
At NO1 compressor startup (outdoor tem-
perature: -15°C[5°F] or more) or at NO2
compressor startup (HP144/HP192 models)
ON for 4 minutes.
After resuming operation after the comple-
tion of the defrost cycle
ON for 8 minutes.
After NO1 compressor startup (outdoor tem-
perature: -15°C[5°F] or lower) or after re-
suming operation after the completion of the
defrost cycle (outdoor temperature:
-15°C[5°F] or lower)
ON when 25 minutes or less have
passed and 63HS1 or 2 < 1.96MPa
[284 psi].
OFF when 25 minutes or more
have passed or 63HS1 or 2
1.96MPa [284 psi].
After resuming operation after Themo mode
or after 3-minute restart delay mode
ON for 4 minutes.
When the compressor stops at cooling/heat-
ing mode
Always ON.
Exception: OFF when 63HS1 or 2 -63LS is 0.2 MPa [29 psi] or less
After the operation has stopped
ON for 3 minutes.
Exception: OFF when 63HS1 or 2 -63LS is 0.2 MPa [29 psi] or less
During defrost cycle
ON
During oil recovery operation
OFF during oil recovery operation (cooling/heating) after low frequency
continuous operation.
During cooling operation, during compres-
sor frequency Fmin operation, or when low
pressure (63LS) drops (3 minutes have
passed since startup)
When low pressure (63LS) drops
below 0.23 MPa [33 psi].
When low pressure (63LS) rises
above 0.38MPa [55 psi].
During heating operation and when low
pressure (63LS) drops (3 minutes have
passed since start up and resuming opera-
tion after the completion of the defrost cycle
.)
When low pressure (63LS) drops
below 0.12 MPa [17 psi].
3 minutes have passed since ON
control started, and when low pres-
sure (63LS) drops below 0.16MPa
[23 psi].
When high pressure (63HS1 or 2) rises
When 63HS1, 63HS2 exceeds
3.62 MPa [525 psi].
When 63HS1, 62HS2 are or below
3.43 MPa [497 psi] and 30 seconds
have passed.
Operation
SV2
ON OFF
At NO1 compressor startup (outdoor tem-
perature: 5°C[41°F] or lower) or after resum-
ing operation after the completion of the
defrost cycle
ON when 5 minutes or less have
passed and 63HS1 < 1.96MPa
[284 psi].
OFF when 5 minutes or more have
passed or 63HS1
1.96MPa [284
psi].
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......