1. Refrigerant
pipe
size
(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe size)
(2) Size of the refrigerant pipe between the first branch and the indoor unit (indoor unit pipe size)
(3) Size of the refrigerant pipe between the branches for connection to indoor units
(4) Size of the refrigerant pipe between the first distributor or the second distributor and outdoor units
Outdoor unit set name
(total capacity)
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
72 model
ø12.7 [1/2"]
ø19.05 [3/4"]
96 model
ø12.7 [1/2"]
ø22.2 [7/8"]
144 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
192 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
model
Pipe diameter (mm) [inch]
06 - 18 models
Liquid pipe
ø6.35 [1/4"]
Gas pipe
ø12.7 [1/2"]
24 - 54 models
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø15.88 [5/8"]
72 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø19.05 [3/4"]
96 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø22.2 [7/8"]
Total capacity of the
downstream units
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
- P54
ø9.52 [3/8"]
ø15.88 [5/8"]
P55 - P72
ø9.52 [3/8"]
ø19.05 [3/4"]
P73 - P108
ø9.52 [3/8"]
ø22.2 [7/8"]
P109 - P144
ø12.7 [1/2"]
ø28.58 [1-1/8"]
P145 - P234
ø15.88 [5/8"]
ø28.58 [1-1/8"]
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
72 model
ø9.52 [3/8"]
ø19.05 [3/4"]
96 model
ø22.2 [7/8"]
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......