IX
Troubleshooting ]
- 138 -
HWE0716A
GB
1. Error
Code
Heatsink overheat protection
2. Error definition and error detection method
When the heat sink temperature (THHS) remains at or above TOH is detected.
3. Cause, check method and remedy
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 196)
4230
Cause
Check method and remedy
(1)
Fan board failure
Refer to 9 [4] - 6 - (2) [6].(page 199)
(2)
Outdoor unit fan failure
Check the outdoor unit fan operation.
If any problem is found with the fan operation, check the fan motor. ->Refer to
9 [4] - 6 - (2) [5].(page 199)
(3)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(4)
THHS failure
Check the THHS sensor reading on the LED monitor.
->If an abnormal value appears, check the sensor resistance, and replace the
sensor as necessary.
Model
TOH
HP72, HP96
90°C[194°F]