1. Error
Code
ACCT sensor circuit fault (Detail code 117)
2. Error definition and error detection method
When an error value is detected with the ACCT detection circuit just before the inverter starts
3. Cause, check method and remedy
Refer to section - 6 -"Inverter" under part [4] "Trouble shootiong principal parts" for error codes related to the
inverter.(page 196)
1. Error
Code
DCCT sensor circuit fault (Detail code118)
2. Error definition and error detection method
When an error value is detected with the DCCT detection circuit just before the inverter starts
3. Cause, check method and remedy
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 196)
5301
Cause
Check method and remedy
(1)
INV board failure
Refer to 9 [4]-6-(2) [1].(page 198)
(2)
Compressor failure
Refer to 9 [4]-6-(2) [2].(page 198)
5301
Cause
Check method and remedy
(1)
Contact failure
Check for good contact of the INV board connector CNCT and the connec-
tor on the DCCT side.
(2)
INV board failure
Refer to 9 [4]-6-(2) [1].(page 198)
(3)
DCCT sensor failure
Replace the DCCT sensor.
(4)
Compressor failure
Refer to 9 [4]-6-(2) [2].(page 198)
(5)
Inverter failure
Refer to 9 [4]-6-.(page 196)
Summary of Contents for City Multi PUHY-HP144TSHMU-A
Page 1: ......
Page 9: ...HWE0716A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 53: ... 44 ...
Page 63: ... 54 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 77: ... 68 ...
Page 83: ... 74 ...
Page 85: ... 76 ...
Page 109: ... 100 ...
Page 125: ... 116 ...
Page 221: ... 212 ...
Page 265: ......