Field Wiring
Table 4 DTC-300A Zone Wiring Chart
5.3
Trouble Output Wiring
The trouble output is wired to a Fire Alarm Trouble Only monitor zone. This is done to monitor
the DTC-300A. The E.O.L resistor required for this zone is to be placed on the terminals
marked E.O.L. below the Trouble Output. The value of the E.O.L. resistor depends on the
FACP used. For the Mircom FACP, use 3K9 ohms. The Trouble Output terminals are dry
contacts. Use JW4 to select either normally closed (pins 1 and 2) or normally open (pins 2 and
3).
Figure 5
DTC-300A Trouble Output Wiring.
Wire gauge
Maximum wiring run to last device
AWG
Feet
Meters
22
2990
910
20
4760
1450
18
7560
2300
16
12000
3600
14
19000
5800
12
30400
9200
Note:
Maximum loop resistance should not exceed 100 ohms.
Maximum capacitance of 0.5
μ
F total on each zone.
i