6
2.0
Introduction and Features
The DTC-300A is a single board Digital Communicator (DACT) that can connect to any Fire
Alarm Control Panel (FACP). It can transmit Alarm, Supervisory, Waterflow Alarm, Common
Trouble, AC power trouble and Battery Trouble information on two telephone lines to a Digital
Alarm Communicator Receiver (DACR).
Features:
•
Scans up to 6 configurable input zones. The input zone type may be alarm, waterflow
alarm, supervisory, trouble, AC trouble or Battery trouble.
•
Reports to a DACR using
Ademco Contact ID
or
SIA DCS
reporting protocols.
•
The DTC-300A has the ability of disconnecting the incoming and outgoing calls and
capturing the line for transmission to the DACR.
•
Provides telephone line monitoring and reports status via LED indication on-board.
•
Provides LED indication for AC Power, Common Trouble, CPU Fail and Ground Fault.
•
User configurable locally with on-board keypad and a
CFG-300 Configuration Tool
or
using a UIMA and computer with serial port or USB. Remotely configurable via a
personal computer, modem and telephone line connection.
•
Provides event logs of 500 entries each to save events from local dialer or remote fire
alarm panel. These logs can be reviewed locally with the CFG-300 Configuration Tool or
remotely via modem.
•
Requires 24V DC filtered or 24V DC Full Wave Rectified (FWR) power supply.