35
12.0
Compatible Fire Alarm Control
Panels
Mircom DTC-300A:
Compatible with
Mircom FA-300 Series, FX-2000 Series and FA-1000
Series
Fire Alarm Control Panels and all other FACP that can provide 24V DC regulated or
24V DC FWR power, 60mA current MIN and 110mA MAX and normally open relay contacts
rated 28V DC, 2A resistive load.
13.0
Compatible Receivers
The
Mircom DTC-300A
is compatible with the following
Digital Alarm Communicator
Receivers (DACR):
14.0
Specifications
All Circuits are Power Limited except 24V DC OUT
DTC-300A Digital Communicator
•
Connects to two Telephone Lines and performs line supervision.
•
Connects to a FACP via input zones and 24V DC regulated or 24V DC FWR power.
•
Transmits user configurable Alarm, Supervisory, and Trouble status to a DACR, using
either Ademco Contact ID or SIA DCS protocols.
•
User configurable locally or remotely. Configuration is passcode protected.
•
Current Consumption:
Standby
: 60 mA
Alarm
: 110 mA
15.0
Battery Calculations
The DTC-300A Battery Calculations are performed as part of the calculations for the Fire
Alarm Control Panel it will be used in. See the appropriate Mircom Installation and Operation
Manual.
DACR Receiver Model
Protocols
SurGard MLR2 Multi-Line Receiver (ULC, ULI Approved)
SIA-DCS and Ademco Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI Approved)
SIA-DCS and Ademco Contact ID
Osborne-Hoffman Quickalert! II Receiver (ULI Approved)
SIA-DCS and Ademco Contact ID
Osborne-Hoffman OH-2000 Receiver (ULI Approved)
SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved)
SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved)
Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved)
SIA-DCS and Ademco Contact ID