15
8.0
Configuration Set-up
There are 3 ways of configuring the DTC-300A.
1. Locally with the on-board keypad and CFG-300 Configuration Tool.
2. Locally with a Personal Computer via the RS-232 connection, a UIMA and Mircom
Software MSW-012.
3. Remotely with a computer, modem, UIMA and Mircom Software MSW-012.
8.1
Configuration via On-Board Keypad
1. Connect 24V DC power supply and zone inputs from the DTC-300A to the fire alarm
panel.
2. Hook up the CFG-300 Configuration Tool ribbon cable to U18 on the DTC-300A board.
3. Hook up the telephone lines and telephone as shown in Figure 3.
4. Power up the fire alarm panel and the message of the CFG-300 Configuration Tool
should be:
5. Place jumper on JW2, located in the bottom right hand corner of the DTC-300A board
(this will generate a trouble on the DTC-300A and report this to the receiver). Press
Menu on the keypad to enter the configuration menu and configure the DTC-300A. The
following screen will ask for the passcode.
6. Enter the default passcode, 1111. Press Enter.
8.2
Configuration via UIMA and Computer (Local)
1. Set-up UIMA connection: the 10-pin cable connector of UIMA is connected to P2 on
DTC-300A board. A serial cable or USB cable is needed to connect the UIMA to the
computer.
2. Place a jumper at JW2 on the DTC-300A board to allow the configuration (a trouble is
generated and reported to the receiver DACR).
3. Start the Mircom Software MSW-012 on the computer to configure the DTC-300A.
Follow the instructions of MSW-012 menu to complete the configuration of the DTC-
300A.
4. Remove jumper on JW2 after configuration is finished, otherwise a trouble will occur.
S/DTC-300A Idle
00:00 SUN 2006-10-01
Enter Passcode
Passcode:_