28
Keypad Configuration & Operation
Command Menu/Dialer-Config/Time Parameter
2.Cellular report date
0 ->Default
Use this menu to set the test
report date for the cell phone
setup. Set this menu to 0 if there
is no test reporting for a cell
phone, or if the phone line is a
regular line. Set this menu from
01 to 28 to schedule a test for
Line 2 on a certain day of the
month. See section 9.11.5 on
page 29 for more information.
When a cell phone service is
employed for the panel, it should
only be connected to telephone
line #2 CO interface. Also, the
dial tone detection feature of
Line 2 should be disabled for cell
phone application.
Command Menu/Dialer-Config/Time Parameter
3.Auto test time
00:30 ->Default
Use this function to set the time
for the automatic test. When this
test is performed, the test report
is sent to the monitoring station.
This test must be performed at
least once a day. The time is in
24 hour format, which means
00:30 is 30 minutes after
midnight.
The Auto test time can be
configured to:
12:00 a.m. to 5:59 a.m.: test
every 24 hours
6:00 a.m. to 11:59 a.m.: test
every 6 hours
12:00 p.m. to 23:59 p.m.: test
every 12 hours
The test alternates between Line
1 and Line 2. See section 9.11.5
on page 29 for more information.
To minimize receiver
congestion, do not use the
following test times: 00:00,
01:55, 02:00 and 03:00.
C e l l u l a r R e p o r t D a t e
0
A u t o - T e s t T i m e
0 0 : 3 0