Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
164
3.5.1 Location drawing of installation foundation of the unit: (unit:
mm)
225
Drainage channel
Anchor bolt
1550
1586
MGBT- F120W/RN1
3.5.1 Location drawing of installation foundation of the unit: (unit:
mm)
230
Drainage channel
Anchor bolt
2388
1888
MGBT- F180W/RN1
350
Schematic diagram of installation dimension of the unit
1551
1551
18
88
Drainage
channel
Hole for anchor bolt
80
Concrete
Cement mortar
Drainage channel
MGBT- F250W/RN1
1.4 Installation of damping devices
Damping devices must be provided between the unit and its foundation.
By means of the Φ15mm diameter installation holes on the steel frame of the unit base, the unit can be
fastened on the foundation through the spring damper. See upper pictures (Schematic diagram of installation
dimension of the unit) for details about center distance of the installation holes. The damper does not go with
the unit, and the user can select the damper according to the relevant requirements. When the unit is installed
on the high roof or the area sensitive to vibration, please consult the relevant persons before selecting the
damper
80
Concrete
Cement mortar
Drainage channel
80
Concrete
Cement mortar
Drainage channel
Summary of Contents for Aqua Tempto Power Series
Page 2: ......
Page 58: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 56...
Page 61: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 59 45...
Page 64: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 62 40...
Page 65: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 63...
Page 73: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 71 57...