Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
144
1.6 MGBT-F250W/RN1
No
,
Code
Trouble
1
E0
Error of outdoor EEPROM
2
E1
Power phase sequence error
3
E2
Communication error
4
E3
Error of total outlet water.temp sensor(Be valid for main unit)
5
E4
Outlet water temp. sensor in Shell and tube exchanger error
6
E5
Pipe temp. sensor in condenser A error
7
E6
Pipe temp. sensor in condenser B error
8
E7
Outdoor ambient temp. sensor error
9
E8
Output of the power protector error
10
E9
Water flow detection error(manual recovery)
11
EA
(Reserved failure code)
12
Eb
Freeze-proof temp. sensor in shell and tube exchanger error
13
EC
Wired controller detect that the units on-line have decreased.
14
Ed
(Reserved failure code)
15
EF
Error of inlet water temp. sensor
16
P0
High pressure or air discharge temp. protection error in system A
17
P1
Low pressure protection System A (manual recovery)
18
P2
High pressure or air discharge temp. protection in system B (manual recovery)
19
P3
Low pressure protection System B (manual recovery)
20
P4
Current protection in system A (manual recovery)
21
P5
Current protection in system B (manual recovery)
22
P6
Condenser high temp. protection in system A
23
P7
Condenser high temp. protection in system B
24
P8
(Reserved failure code)
25
P9
Protection of outlet and inlet water temp. difference
26
PA
Low ambient temp. drive-up protection
27
Pb
System freeze-proof protection
28
PC
Anti-freezing pressure protection of the system A (manual recovery)
29
Pd
Anti-freezing pressure protection of the system B (manual recovery)
30
PE
Low-temp. protection of evaporator (manual recovery)
Summary of Contents for Aqua Tempto Power Series
Page 2: ......
Page 58: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 56...
Page 61: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 59 45...
Page 64: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 62 40...
Page 65: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 63...
Page 73: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 71 57...