Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
154
12) The unit inlet water temperature sensor malfunction
13) Pipe temp. sensor of condenser malfunction
The unit inlet water temperature
sensor malfunction
Inform
the
customer service
center.
PCB mistakes to alarm.
The unit
’s circuit of inlet water
temperature sensor is broken.
Replace PCB.
Replace temperature sensor.
The unit
’s circuit of inlet water
temperature sensor is shorten.
Replace temperature sensor.
The unit
’s joint of inlet water
temperature sensor is loose.
Fixed joint.
No
Yes
Yes
Yes
Yes
Yes
No
No
No
Pipe
temperature
sensor
of
condenser malfunction.
Inform
the
customer service
center.
PCB mistakes to alarm.
The circuit of condenser
’s pipe
temperature sensor is broken.
Replace PCB.
Replace temperature sensor.
The circuit of condenser
’s pipe
temperature sensor is shorten.
Replace temperature sensor.
The joint of condenser
’s pipe
temperature sensor is loose.
Fixed joint.
No
Yes
Yes
Yes
Yes
Yes
No
No
No
Summary of Contents for Aqua Tempto Power Series
Page 2: ......
Page 58: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 56...
Page 61: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 59 45...
Page 64: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 62 40...
Page 65: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 63...
Page 73: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 71 57...