MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
173
Water flow switch
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
No.1 unit
No.0 address(main unit)
No.n unit (n
≤8)
No.(n-1) unit
No.(2n-3) address
No.(2n-1) address
No.1 address
No.(2n-4) address
No.(2n-2) address
Pump
Installation mode B: less than 8 modules
Notices :
1) For installation of multi-module, the most modules should be not more than 8 modular units.
2) For installation of multi-module, please drill a dead hole(
Φ
9mm) at the total water outlet pipeline,
and move the total water effluent temp. sensor at No.0 address to the hole.
3.4 MGBT-F180W/RN1
Installation of single-module water system pipeline
Total water outlet temperature sensor
Water outlet
Water inlet
Electric control box
Multi-module combination installation involves special design of the unit, so relevant explanation is
given as follows.
Installation mode of multi-module combination water system pipeline