3 Typical malfunction solutions
1) High pressure and discharged temperature protection
Yes
No
No
Yes
Yes
Yes
Yes
Yes
High pressure and
discharged protection.
No
No
Yes
Yes
Yes
Yes
No
No
No
No
High
pressure
protection.
Blower stops rotating or rotates in
reversed direction in cooling mode,
water pump is not open or the flow.
Couldn’t start the EXV.
Pressure controller is broken
or the joint is loose.
Fin heat exchanger in cooling mode is too
dirty or aged, or too heavy encrustation in
shell and tube for heating.
EXV, capillary and filter are
dirty, blocking.
Discharge
temperature
protection.
See
the
analysis
of
discharge temp. protection
malfunction.
Inspect fan motor and
capacitor
(1phase)
or
start up the water pump.
Replace EXV or coil.
Replace press controller,
fixed joint.
Clean heat exchanger.
Replace EXV, capillary
and filter.
There is air and filled refrigerant
too much in system.(Generally
occur after maintenance.)
PCB mistakes to alarm.
Empty, vacuuming and
append refrigerant if
necessary.
Check if it happened
frequently, if yes, please
replace PCB.
Inform
the
customer
service center.
Summary of Contents for Aqua Tempto Power Series
Page 2: ......
Page 58: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 56...
Page 61: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 59 45...
Page 64: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 62 40...
Page 65: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 63...
Page 73: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 71 57...