Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
162
Input of airflow
Input of airflow
A
B
C
D
Input of airflow
Input of airflow
E
MGBT- F250W/RN1
The recommend space parameter
Module
Installation space (mm)
A
B
C
D
E
MGBT-F25W/RN1
≥1500
≥2000
≥1500
≥2000
≥8000
MGBT-F30W/RN1
MGBT- D25W/RN1
MGBT- D30W/RN1
MGBT-F60W/RN1
MGBT-D60W/RN1
MGBT-F120W/RN1
MGBT-F180W/RN1
≥2000
≥2000
MGBT-F250W/RN1
● Space requirements for parallel installation of multiple modular units
To avoid back flow of the air in the condenser and operational faults of the unit, the parallel installation of
multiple modular units can follow the direction A and D as shown in the figure above, the spaces between the
unit and the obstacle are given in the figure above, and the space between adjacent modular units should not
be less than 300mm; the installation can also follow the direction B and C as shown in the figure above, the
spaces between the unit and the obstacle are given in the figure above, and the space between adjacent
modular units should not be less than 600mm; the installation can also follow the direction combination of A
Summary of Contents for Aqua Tempto Power Series
Page 2: ......
Page 58: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 56...
Page 61: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 59 45...
Page 64: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 62 40...
Page 65: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 63...
Page 73: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 71 57...