Microtronix Access User Guide
●
Internally mounted 32GB flash drive (standard with CDR Collection Manager)
●
-48VDC AC adapter
2.2 Location
Select a location for the Access Gateway that meets the following requirements:
●
Complies with the Environment and Electrical Requirements outlined in this section.
●
Is within cabling distance of the network equipment and power connections.
●
Does not have restricted airflow. There must be at least 2 inches clearance on all sides so that
proper air ventilation is not obstructed. If space is at a premium, you may place light equipment,
such as the network modem, on top of the unit.
●
Permits access to the back of the unit to allow user to make cable connections.
2.3 Mounting
The Access Gateway may be placed on any flat surface or shelf provided that the unit is within 3 feet of
an AC power source. At least 2” of space on each side of the unit is required to ensure proper air flow.
The physical dimensions (D x W x H) and nominal weight of the Access Gateways are:
●
Model 1000-S04 – 3.6” x 4.25” x 1.25” (9.2 x 10.8 x 3.2 cm), 0.5 lb (0.22 kg)
●
Model 4002-S04 - 5.5” x 7.25” x 1.6” (14 x 18.5 x 4 cm), 1.4 lb (0.64 kg).
●
Model 4002-N04-RM – 5.4” x 14” x 1.72”, 4 lb
●
Model 4002-N44-RM - 5.4” x 14” x 1.72”, 4 lb
2.4 Electrostatic Considerations
All microcomputers are sensitive to electrostatic discharges (ESD). A direct ESD discharge to the
chassis or cables can disrupt unit operation, induce a latent failure condition, or even permanently
damage circuit components. For these reasons, you must use good ESD control procedures that
electrically ground you when making direct physical contact with the unit or cables. The use of
grounding wrist straps and cords is strongly recommended for controlling discharges and preventing
ESD damage.
WARNING:
To prevent damage to port drivers and receivers, you must use proper electrostatic control
precautions when attaching or handling cables.
2.5 Environmental Specifications
The environmental specifications recommended for maximum reliability of the Access Gateway are:
Ambient Temperature
5 to 50 degrees C (For short term operation to 55 degrees C)
Temperature rate of change
3 degrees / hour
Humidity
10% to 95% (non-condensing)
Humidity rate of change
2% / hour