INSTALLATION AND WIRING
(2) Terminal block layout
In the control circuit of the inverter, the terminals are arranged as shown below:
Terminal screw size: M2.5
(3) Wiring method
1) For wiring the control circuit, use cables after stripping their sheaths.
Refer to the gauge printed on the inverter and strip the sheaths to the following
dimensions. If the sheath is stripped too much, its cable may be shorted with the
adjoining cable. If the sheath is stripped too little, the cable may come off.
2) When using bar terminals and solid wires for wiring, their diameters should be 0.9mm
maximum. If they are larger, the threads may be damaged during tightening.
3) Loosen the terminal screw and insert the cable into the terminal.
4) Tighten the screw to the specified torque.
Undertightening can cause cable disconnection or misoperation. Overtightening can
cause damage to the screw or unit, leading to short circuit or misoperation.
Tightening torque: 0.25N
⋅
m to 0.49N
⋅
m
*Use a size 0 screwdriver to tighten.
Note: When routing the stripped cables, twist them so that they do not become loose.
In addition, do not solder it.
RH
RM
RL
MRS
RES
SD
AM
PC
SE
RUN
FU
A
B
C
10
2
5
4
SD
STF
STR
SD
Terminal layout of control circuit
7mm
±
1mm (0.28inch
±
0.04inch)