INSTALLATION AND WIRING
(4) Control logic changing
The input signal logic is factory-set to the sink logic.
To change the control logic, the position of the jumper connector must be changed.
1) Use tweezers etc. to remove the jumper connector in the sink logic position and fit it
in the source logic position.
Do this position changing before switching power on.
Note: 1. Make sure that the front cover has been installed securely.
2. The front cover has a capacity plate and the inverter a rating plate on it.
Since these plates have the same serial numbers, always reinstall the
removed cover to the inverter from where it was removed.
3. Always install the sink-source logic changing jumper connector in either of
the positions. If two connectors are installed in these positions at the same
time, the inverter may be damaged.
Jumper
connector