147
4
PARAMETERS
4.2.41 Actual operation hour meter clear (Pr. 171)
Pr. 171 "actual operation hour meter
clear"
You can clear the monitor (actual operation hour) value which is selected when Pr. 52 is
"23".
<Setting>
Write "0" in the parameter to clear the actual operation hour.
4.2.42 Input terminal function selection (Pr. 180 to Pr. 183)
Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "MRS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter
Number
Factory
Setting
Setting
Range
171
0
0
Pr. 173 to Pr. 176
Refer to Pr. 160.
Parameter
Number
Terminal
Symbol
Factory
Setting
Factory-Set Terminal
Function
Setting
Range
180
RL
0
Low-speed operation
command (RL)
0 to 8, 16, 18
181
RM
1
Middle-speed operation
command (RM)
0 to 8, 16, 18
182
RH
2
High-speed operation
command (RH)
0 to 8, 16, 18
183
MRS
6
Output shut-off (MRS)
0 to 8, 16, 18
Pr. 52 "operation panel/PU main
display data selection"
Related parameter
M4500E.book 147 ページ 2005年2月22日 火曜日 午後5時7分