PROTECTIVE FUNCTIONS
Operation Panel Indication
E. RET
FR-PU04-MGI
Retry No Over
Name
Retry count exceeded
Description
If operation cannot be resumed properly within the number of
retries set, this function stops the inverter output.
Check point
Find the cause of alarm occurrence.
Corrective action
Eliminate the cause of the error preceding this error indication.
Operation Panel Indication
E. CPU
FR-PU04-MGI
CPU Fault
Name
CPU error
Description
If the arithmetic operation of the built-in CPU does not end
within a predetermined period, the inverter self-determines it
as an alarm and stops the output.
Check point
———
Corrective action
Please contact your sales representative.
Operation Panel Indication
E. 3
FR-PU04-MGI
Fault 3
Name
Option fault
Description
Also stops the inverter output if the dedicated option used in
the inverter results in setting error or connection (connector)
fault.
Check point
• Check that the function setting and operation of the option
are correct.
• Check that the communication option is plugged in the
connector securely.
• Check for devices producing excess electrical noises around
the inverter.
Corrective action
• Connect the communication option securely.
• Take measures against noises if there are devices producing
excess electrical noises around the inverter.
• Contact your sales representative.
Operation Panel Indication
E. 6
FR-PU04-MGI
Fault 6
E. 7
Fault 7
Name
CPU error
Description
This function stops the inverter output if a communication error
occurs in the built-in CPU.
Check point
Check for devices producing excess electrical noises around
the inverter.
Corrective action
• Take measures against noises if there are devices producing
excess electrical noises around the inverter.
• Please contact your sales representative.