Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
F - 27
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
F.2.9 Output configuration – factory
describes the SpeedSys300 ODS301 Modbus registers related to the module
output configuration – factory.
NOTE:
This data block is intended/reserved for factory use only and should not be
changed by end-users.
NOTE:
The Modbus registers in this data block are read/write.
Key:
n.u. – Not used.
Table F-14:
SpeedSys300 ODS301 Modbus registers – output configuration – factory
Address
Name
Data
type
Range
Access
Description
6000
cal_aout_4ma
uint16
100 to 24000
Level 2
PWM value for 4 mA
6001
cal_aout_20ma
uint16
100 to 24000
Level 2
PWM value for 20 mA
6002
cal_ain_4ma
uint16
0 to 16383
Level 2
Current readback for 4 mA
6003
cal_ain_20ma
uint16
0 to 16383
Level 2
Current readback for 20 mA
6004
v_max
single
0 to 2100000
Level 2
Max. limit for speed settings
6006
v_min
single
0 to 2100000
Level 2
Min. limit for speed settings
6008
acc_max
single
−100000 to
100000
Level 2
Max. limit for acceleration settings
6010
acc_min
single
−100000 to
100000
Level 2
Min. limit for acceleration settings
6012
Reserved
uint16
Level 2
6013
crc_diag_fact
uint16
Level 2
Parameter block CRC