Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
F - 15
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
F.2.4 Device configuration – factory
describes the SpeedSys300 ODS301 Modbus registers related to the module
configuration – factory.
This data block is intended/reserved for factory use only and should not be changed by
end-users.
NOTE:
The Modbus registers in this data block are read/write.
F.2.5 Measurement configuration
describes the SpeedSys300 ODS301 Modbus registers related to the module
measurement configuration.
NOTE:
The Modbus registers in this data block are read/write.
Table F-9:
SpeedSys300 ODS301 Modbus registers – module configuration – factory
Address
Name
Data
type
Range
Access
Description
3000
serial_number
char16
Level 2
3008
schem_version
char16
Level 2
3016
PCB_code
char16
Level 2
3024
device_option
uint16
Level 2
Module personality (bit pattern):
0011b – SpeedSys300 ODS301.
3025
crc_dev_fact
uint16
Level 2
Parameter block CRC
Table F-10:
SpeedSys300 ODS301 Modbus registers – measurement configuration
Address
Name
Data
type
Range
Access
Description
4000
wheel_shape
uint16
0 to 3
Level 1
Type of wheel.
(For information only.)
4001
wheel_teeth
uint16
1 to 10000
Level 1
Number of pulses per revolution
4002
sensor_type
uint16
0 to 2
Level 1
Sensor type:
0 – 2-wire current
1 – 3-wire voltage
2 – 2-wire voltage.
4003
freq_avr
uint16
1 to 1000
Level 1
Frequency averaging window for frequency
measurement
4004
freq_avr_acc
uint16
1 to 1000
Level 1
Frequency averaging window for
acceleration measurement
Summary of Contents for vibro-meter SpeedSys300 ODS301