![Meggitt vibro-meter SpeedSys300 ODS301 User Manual Download Page 21](http://html1.mh-extra.com/html/meggitt/vibro-meter-speedsys300-ods301/vibro-meter-speedsys300-ods301_user-manual_1765658021.webp)
Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
1 - 3
System overview
INTRODUCTION TO THE SPEEDSYS300 ODS301 OVERSPEED DETECTION SYSTEM
See also
for more detailed information on the SpeedSys300 ODS301 module’s
electrical interfaces (sensor), suitable for wiring sensors / measurement chains to a module.
SpeedSys300 ODS301 module
Magnetic
sensor
(Max. length: 30 m approx.)
(Max. length: 300 m approx.)
(Max. length: 1000 m approx.)
Electronic
sensor
Proximity
sensor
Power supply 1
(PSU 1)
Power supply 2
(PSU 2)
Proof test
(control) input
Binary (status)
output
Serial
communications
interface (RS-485)
USB
(for communications with the
SpeedSys300 software)
Analog output
*
(4 to 20 mA)
Frequency (speed)
output
Safety relay 1
*
(relay 1)
Safety relay 2
*
(relay 2)
Additional relay 3
(relay 3)
Additional relay 4
(relay 4)
V+
V
−
BR
BR
V+
SIG
V
−
IS
I+
I
−
IS
IS
(Signal
conditioner)
V+
V0
IE
IE
V+
V0
IE
IE
IN
GND
MA+
MA
−
FREQ+
FREQ
−
OUT
GND
DATA A
DATA B
GND
K4
K4
K3
K2-2
K1-2
K2-1
K1-1
USB Mini-B
Figure 1-2:
SpeedSys300 ODS301 module – interfaces
Notes
The SpeedSys300 ODS301 module
is a single channel device. It has
three separate input interfaces for
connection to different types of
speed sensor / measurement chain
but only one measurement channel
can be configured and used by the
module at any one time.
*
Only Safety relay 1, Safety relay 2
and the Analog output are safety
outputs. No other outputs should be
used to implement a safety function.
IE