![Meggitt vibro-meter SpeedSys300 ODS301 User Manual Download Page 33](http://html1.mh-extra.com/html/meggitt/vibro-meter-speedsys300-ods301/vibro-meter-speedsys300-ods301_user-manual_1765658033.webp)
Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
2 - 9
SpeedSys300 ODS301 module connectors
OVERVIEW OF THE SPEEDSYS300 ODS301 MODULE HARDWARE
Connector pinouts (definition of terminals) for the 3 connectors on the top of the module are
given in
to
Table 2-3:
SpeedSys300 ODS301 module 2-WIRE VOLTAGE connector pinouts
SpeedSys300 ODS301 2-WIRE VOLTAGE connector
Label
Pin
Name /
function
Direction
Definition
2-
W
IRE
V
O
LTAGE
B01
V+
I
Magnetic sensor interface: Signal
B02
V−
I
Magnetic sensor interface: GND
B03
BR
B
Bridge (short-circuit) to B04
B04
BR
B
Bridge (short-circuit) to B03
Notes
B = bidirectional, GND = ground, I = input.
Table 2-4:
SpeedSys300 ODS301 module 3-WIRE VOLTAGE connector pinouts
SpeedSys300 ODS301 3-WIRE VOLTAGE connector
Label
Pin
Name /
function
Direction
Definition
3-
W
IRE
V
O
LTAGE
B05
V+
O
Electronic sensor interface: Power supply
B06
SIG
I
Electronic sensor interface: Signal
B07
V−
B
Electronic sensor interface: GND
B08
IS
B
Intrinsically safe earth / GND
Notes
B = bidirectional, GND = ground, I = input, IS = Intrinsically safe, O = output.
Table 2-5:
SpeedSys300 ODS301 module 2-WIRE CURRENT connector pinouts
SpeedSys300 ODS301 2-WIRE CURRENT connector
Label
Pin
Name /
function
Direction
Definition
2-
WI
R
E
CURRE
NT
B09
I+
I
Proximity sensor (current loop) interface: Power supply
B10
I−
I
Proximity sensor (current loop) interface: GND
B11
IS
B
Intrinsically safe earth / GND
B12
IS
B
Intrinsically safe earth / GND
Notes
B = bidirectional, GND = ground, I = input, IS = Intrinsically safe.