USER MANUAL
Document reference MAODS301/E
SpeedSys300 ODS301 overspeed detection system
Edition 4 - May 2022
3 - 18
Installation considerations
INSTALLATION OF A SPEEDSYS300 ODS301
3.2.9 Electrical interfaces
shows the electrical interfaces for the product.
The sensor / input channel interfaces (proximity, electronic and magnetic) on the left side of
(See also
for more detailed information on all of the SpeedSys300 ODS301
module’s hardware interfaces.)
As shown in
, the use of a 2-wire voltage sensor (magnetic
sensor) requires a bridge (short-circuit) to be set between the BR contacts
of the 2-WIRE VOLTAGE connector (see
In case of the 2-wire voltage (magnetic) sensor not being used, the bridge
must be removed in order to ensure full functionality of the module.
Refer to the
SpeedSys300 ODS301 overspeed detection system data sheet
for further information before connecting any electrical interfaces.
Figure 3-8:
SpeedSys300 ODS301 electrical interfaces
Notes
*
For 2-wire voltage (magnetic) sensor,
install the SpeedSys300 ODS301 module in
a controlled electromagnetic environment or
connect both sides of sensor cable shield to
intrinsically safe earth.
Notes
The SpeedSys300 ODS301 module is a
single channel device. It has three separate
input interfaces for connection to different
types of speed sensor / measurement chain
but only one measurement channel can be
configured and used by the module at any
one time.