USER MANUAL
Document reference MAODS301/E
SpeedSys300 ODS301 overspeed detection system
Edition 4 - May 2022
F - 26
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
5616
r1_acc_max_hyst
single
acc_min to
acc_max
Level 1
Relay 1 max. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5618
r2_acc_max_hyst
single
acc_min to
acc_max
Level 1
Relay 2 max. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5620
r3_acc_max_hyst
single
acc_min to
acc_max
Level 1
Relay 3 max. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5622
r4_acc_max_hyst
single
acc_min to
acc_max
Level 1
Relay 4 max. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5624
do_acc_max_hyst
single
acc_min to
acc_max
Level 1
Digital out max. acceleration alarm
hysteresis.
Range defined in ‘Output config - factory’.
5626
r1_acc_min_hyst
single
acc_min to
acc_max
Level 1
Relay 1 min. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5628
r2_acc_min_hyst
single
acc_min to
acc_max
Level 1
Relay 2 min. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5630
r3_acc_min_hyst
single
acc_min to
acc_max
Level 1
Relay 3 min. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5632
r4_acc_min_hyst
single
acc_min to
acc_max
Level 1
Relay 4 min. acceleration alarm hysteresis.
Range defined in ‘Output config - factory’.
5634
do_acc_min_hyst
single
acc_min to
acc_max
Level 1
Digital out min. acceleration alarm
hysteresis.
Range defined in ‘Output config - factory’.
5636
acc_cutoff_speed
single
v_min to
v_max
Level 1
Minimal speed for acceleration alarm
processing. Below this speed acceleration
alarms are not evaluated.
5638
aout_v_4ma
single
0 to 2100000
Level 1
Speed value for 4 mA output.
Range defined in ‘Output config - factory’.
5640
aout_v_20ma
single
0 to 2100000
Level 1
Speed value for 20 mA output.
Range defined in ‘Output config - factory’.
5642
aout_max
single
3.6 to 21.0
Level 1
Max limit value for Aout swing
5644
aout_min
single
3.6 to 21.0
Level 1
Min limit value for Aout swing
5646
aout_error
single
0 to 3.6
Level 1
Analog output error value
(that is, output value in safe state)
5648
Reserved
uint16
Level 1
5649
crc_out_adm
uint16
Level 1
Parameter block CRC
Table F-13:
SpeedSys300 ODS301 Modbus registers – output configuration – admin (continued)
Address
Name
Data
type
Range
Access
Description
Summary of Contents for vibro-meter SpeedSys300 ODS301