20
RE
- Resistenza elettrica integrata all’interno dell’unità + termostato di sicurezza “TS”
(senza relay di potenza) 230V/50Hz/1Ph.
- Electrical heater integrated inside the units + “TS” safety thermostat (without power
relay) 230V/50Hz/1Ph.
QR1
- Quadro elettrico per sezione elettrica 230Vac (BOX + magnetot relè).
- Power electric board for heaters 230Vac (BOX + magnetot relè).
Modello
Model
Potenza
Power
Compatibilità HCN
HCN compatibility
Compatibilità QR1
QR1 compatibility
RE0.7-24
0,7 kW / 3,1 A
Tutte le taglie - All sizes
QR1-0,7
RE1.0-24
1,0 kW / 4,4 A
Tutte le taglie - All sizes
QR1-1,4
RE1.5-24
1,5 kW / 6,6 A
Tutte le taglie - All sizes
QR1-2,3
RE2.0-24
2,0 kW / 8,7 A
Tutte le taglie - All sizes
QR1-2,3
RE3.0-24
3,0 kW / 13,1 A
HCN 103-130-150-136-170-20 0
QR1-3,7
Modelli/Models
HCN 60
HCN 75
HCN 86
HCN 103
HCN 130
HCN 150
HCN 136
HCN 170
HCN 200
Dimensioni/
Dimensions
Versioni – Versions S
LxA mm
L=800 x A=250
L=1.200 x A=250
L=1.600 x A=250
Versioni – Versions D
LxA mm
L=840 x A=290
L=1.240 x A=290
L=1.640 x A=290
Serranda di regolazione - Regulation louver
BxC mm
B=700 x C=210
B=1.100 x C=210
B=1.500 x C=210
S2S-S
S2S-D
- Sezione chiusa + 2 serrande di regolazione / taratura (1 inferiore + 1 posteriore) -
serrande senza comandi, predisposte per comando manuale o motorizzazione
(S=semplice lamiera zincata, D=doppio pannello preverniciato).
- Closed s 2 Regulation/adjustment louvers (1 louver below + 1 louver on the
rear side) - Louvers without controls - can be either manual or motorized control
(S=single skin panel made of
galvanized steel, D=double skin panel pre-painted).
MS
- Servomotore “230 Vac on/off” per serranda aria.
- Motor “230Vac on-off” suitable for air damper.
SSM-S
SSM-D
- Sezione di miscela aria esterna (0-33%) / interna (100-67%) o viceversa (serrande
coniugate con comandi manuali predisposte per la motorizzazione) (S=semplice
lamiera zincata, D=doppio pannello preverniciato).
- External/Internal mixing section “externail air 0-33% - internal air 100-67% or vice
versa (coupled louvers with manual controls - can be motorized) (S=single skin panel
made of galvanized steel, D=double skin panel pre-painted).
Perdita di carico aria - Air press. drop
Pa(*)
13
15
14
20
24
22
20
24
22
SFA-S
SFA-D
- Filtro aria piano semplice estraibile (non canalizzabile) EU3 (S=semplice lamiera
zincata, D=doppio pannello preverniciato).
- Flat air filter (not ductable), EU3 filtering level. (S=single skin panel made of
galvanized steel, D=double skin panel pre-painted).
P.d.c. aria (filtro pulito/sporco)-Air press.drop (clean/dirty filter) Pa(*)
15/35
17/42
16/38
23/55
27/66
25/60
22/54
28/66
25/60
SFC-S
SFC-D
- Sezione filtro EU3 aria canaliz filtro aria piano (S=semplice lamiera zincata,
D=doppio pannello preverniciato).
- Ductable air filter s flat air filter, EU3 filtering level (S=single skin panel made
of galvanized steel, D=double skin panel pre-painted).
P.d.c. aria (filtro pulito/sporco)-Air press.drop (clean/dirty filter) Pa(*)
15/35
17/42
16/38
23/55
27/66
25/60
22/54
28/66
25/60
SFD-S
SFD-D
- Sezione filtro EU5 aria canaliz filtro aria ondulato H=100mm ALTA EFFICIENZA
(S=semplice lamiera zincata, D=doppio pannello preverniciato).
- Ductable air filter section + HIGH EFFICIENCY ondulated air filter H=100mm, EU5
filtering level (S=single skin panel made of galvanized steel, D=double skin panel pre-
painted).
P.d.c. aria (filtro pulito/sporco)-Air press.drop (clean/dirty filter) Pa(*)
20/37
24/44
22/41
32/59
38/70
35/64
31/58
39/71
35/64
A
L
555
SSL-D
SSL-D
- Sezione silenziatore a labirinto per aspirazione e/o mandata aria (S=semplice
lamiera zincata, D=doppio pannello preverniciato).
- Labyrint noise level attenuator section, suitable for both air intake/supply outlets
(S=single skin panel made of galvanized steel, D=double skin panel pre-painted).
Attenuazione – Attenuation
dB(A)
6 dB(A) 6 dB(A) 6 dB(A) 7 dB(A) 7 dB(A) 7 dB(A) 8 dB(A) 8 dB(A) 8 dB(A)
Perdita di carico aria –Air pressure drop
Pa(*)
23
28
26
37
44
40
36
44
40
Summary of Contents for HCN 103
Page 23: ......