101
Step 3
Disconnect the ice thickness probe from the
control board terminal. Clip the jumper wire to the
terminal on the control board and any cabinet ground.
Monitor the harvest light.
Step 3 Jumper wire connected from control board
terminal to ground
Monitoring Harvest Light
Correction
The harvest light comes on,
and 6-10 seconds later, ice
machine cycles from freeze
to harvest.
The ice thickness probe is
causing the malfunction.
The harvest light comes on
but the ice machine stays in
the freeze sequence.
The control circuitry is
functioning properly. The
ice machine is in a six-
minute freeze time lock-in
(verify step 1 of this
procedure was followed
correctly).
The harvest light does not
come on.
The control board is
causing the malfunction.
GROUND
JUMPER WIRE
ICE THICKNESS
PROBE
PROBE
CONNECTION
EVAPORATOR
HARVEST LIGHT
(RED)
BIN SWITCH
LIGHT
(GREEN)
SV1592J